RFQ/OBP543/2024/25

service of transformers and mini-sub
RFQ/OBP543/2024/25
1 1000kVA Transformer Serial No's 0/5870/1/1 & 0/5870/1/2 2 11000/400V MAIN Clean Transformer Service Seal leaks Change oil 2 500kVA Transformer Serial No. 41992 1 11000/400V BOILER Clean Transformer Service Seal leaks Change oil 3 100kVA Mini Substation Serial No. M7469/1 1 11000/400V COLDROOM Clean Transformer Take Oil Sample, test for kV, Moisture, DGA, PCB and Furanics Attend to Minor Leaks (To Report ONLY on Major) Take After Sample for Analysis (kV & Moisture) repaint with original Colour Service and Test Hawker Siddeley Tiger Switch 4 630kVA Mini Substation Serial No. M6103 1 1 11000/400V EA Clean Transformer Attend to Minor Leaks (To Report ONLY on Major) Change oil repaint with original Colour Service and Test Hawker Siddeley Tiger Switch, including oil Change 5 11kV Substation SWITCH GEAR MAIN & BOILER 2 Clean Panels and Substation Room Service and Test Actom SBV4 Breakers Service includes : Contact Resistance test, AC Pressure test, cleaning, Lubrication and inspection of operating Mechanism. Breaker Speed test and Secondary Injection Testing. Replace indicator lights (change MV fuses if necessary) 6 Service and test Battery Tripping Units, check charge Rate (change battery) 2
Request for Quote
2025/03/16 15:00:00
2025/03/10 11:00:00